SubMonitor is designed to protect 3-phase pumps/motors with service factor amp ratings (SFA) from 5 to 350 A (approx. 3 to 200 hp). Current, voltage, and motor temperature are monitored using all three legs and allows the user to set up the SubMonitor quickly and easily.
In some installations, power supply limitations make it necessary or desirable to increase the power factor of a submersible motor. Table 32 lists the capacitive kVAR required to increase the power factor of large Franklin three-phase submersible motors to the approximate values shown at maximum input loading.
Capacitors must be connected on the line side of the overload relay, or overload protection will be lost.
MOTOR | KVAR REQUIRED FOR PF OF | |||
HP | KW | 0.9 | 0.95 | 1 |
5 | 3.7 | 1.2 | 2.1 | 4 |
7.5 | 5.5 | 1.7 | 3.1 | 6 |
10 | 7.5 | 1.5 | 3.3 | 7 |
15 | 11 | 2.2 | 4.7 | 10 |
20 | 15 | 1.7 | 5 | 12 |
25 | 18.5 | 2.1 | 6.2 | 15 |
30 | 22 | 2.5 | 7.4 | 18 |
40 | 30 | 4.5 | 11 | 24 |
50 | 37 | 7.1 | 15 | 32 |
60 | 45 | 8.4 | 18 | 38 |
75 | 55 | 6.3 | 18 | 43 |
100 | 75 | 11 | 27 | 60 |
125 | 93 | 17 | 36 | 77 |
150 | 110 | 20 | 42 | 90 |
175 | 130 | 9.6 | 36 | 93 |
200 | 150 | 16 | 46 | 110 |