Cable Selection - 60 °C Six-Wire

Table 18 Three-Phase 60 °C Cable (Continued)
MOTOR RATING60 °C INSULATION - AWG COPPER WIRE SIZEMCM COPPER WIRE SIZE
VOLTSHPKW1412108643210000000000250300350400500
200 V
60 Hz
Three-
Phase
6-
Lead
Y-D
53.71602504206601030162020202490306037304570550066607540
7.55.5110180300460730115014401770217026503250390047205340
107.580130210340550850108013201630199024602950358040804650522057006630
1511001402403705807309001110136016602010244027703150352038504470
2015000170280450570690850105012901570190021602470277030303540
2518.500014022036045055069085010501260154017501990225024602850
302200001802943704605707008701050127014501660187020402380
230 V
60 Hz
Three-
Phse
6-Lead
Y-D
53.72103405508801380214026803280403049306040727088009970
7.55.5150240390630970153019002340288035104300516062407060801089509750
107.51101802804607301140142017502160264032403910474053806150690075308760
15110019031049078097012001470180022002670322036604170466051005910
2015001402303706007509101140139017102070252028603270367040204680
2518.5000190300480600750910112013801680204023102640297032403780
302200015024039049061076093011401390169019202200247027003160
380 V
60 Hz
Three-
Phase
6-
Lead
Y-D
53.7600960151023803730580071708800
7.55.540066010301630256039604890600073909010
107.5300480760120018702890357043605350649078409390
15112103405508801380214026503250403049306000726086509780
2015160260410660105016302020250030903790463056406750766042609760
2518.502103305408501320165020202500307037604560546061907080787086109880
3022002704307001090136016802070255031203780453051405880654071508230
403000032051079099012301510186022802760330037504270475052005980
50370002504006308109901230150018302220265030103430382041704780
604500003405406608401030127015401870225025502910322035204050
755500000450550690855105012901570190021602490277030403520
100750000004205206407609401140136015401770196021402470
125930000000400490600730930111012601420159017401990
1501100000000042051062075093010501180132014401630
175130000000003604405406607809701120126013801600
2001500000000000480580690790940105011401320
460 V
60 Hz
Three-
Phase
6-
Lead
Y-D
53.788014202250354055508620
7.55.56301020160025303960615076509390
107.54607501180187029404570570070208620
151131051081012702010313039004800589072108850
201523038061097015402410300037004560559068708290
2518.5190310490790124019502430298036704510555067008140
3022025041064010201600199024603040373045905550675076908790
4030003004807501180147018102230274033704060493055906370
5037000370590960120014701810222027103280397045105130574062707270
6045000320500810100012401530187023102770336038104330486053106150
7555000042066081010201260154018902280277031503600405044205160
1007500000500610760930114014101690207023402680301032803820
1259300000047059073088011101330150018302080234025502940
15011000000005106307709501140138015701790200021802530
175130000000005506808301000122013901580178019502270
200150000000000590730880107012101380155016901970
575 V
60 Hz
Three-
Phase
6-
Lead
Y-D
53.713802220349055208620
7.55.59901590252039706220
107.5730117018602920459071508910
151149079012702010313048906090
20153706109701540241037804710579071408740
2518.53004907801240195030403790466057607060
3022240400645102016002500312038404740582071508670
403003004807501180186023102850349042905260634077108740
503700380590960150018702310283034604260513062107050801089809790
60450005007901270159019502400294036004330525059506780760082909610
75550004206601030129015901960240029503570433049305620633069108050
10075000040078096011801450178021902650322036604180471051405980
12593000006007409201150142017402100253028803270366039704600
150110000000650800990121014801780216024502790312034103950
1751300000000700860106013001570191021702480278030403540
2001500000000076093011401370167018902160242026403070
  • Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details.
  • NOTE: Wire tables are based on copper wire. If aluminum wire is used, it must be two sizes larger than copper wire and oxidation inhibitors must be used on connections.